Free EPA 608 Type 3 Practice Test

By BRIX Editorial Team · Updated

The EPA 608 Type III section covers low-pressure appliances, mainly centrifugal chillers using refrigerants like R-123, R-11 and R-245fa. Because these systems run partly in a vacuum, leaks pull air in instead of pushing refrigerant out, and the test covers purge units, hot-water leak testing, recovery, recharging and the 25 mm Hg evacuation level. It's 25 questions plus 25 Core.

Key takeaways

  • Type III is for low-pressure chillers: refrigerants below 45 psia at 104 °F.
  • Low-pressure systems leak air in, so excessive purging is the classic leak sign.
  • Evacuate to 25 mm Hg absolute before a major repair, whatever the age of your recovery equipment.
  • These are original practice questions, not real exam questions.
Free practice test

EPA 608 Type III practice questions

28 original questions. Study mode shows the answer and explanation after each question. Exam mode gives you 25 random questions and scores you at the end. No sign-up; progress saves in this browser.

Sample questions

  1. 1. What makes an appliance "low-pressure" under the Section 608 definitions?

    • A. It uses a refrigerant with a liquid-phase saturation pressure below 45 psia at 104 °F
    • B. It runs below 100 psig on the high side
    • C. It has a centrifugal compressor
    • D. It holds less than 50 pounds of refrigerant
    Show answer and explanation

    Answer: A. It uses a refrigerant with a liquid-phase saturation pressure below 45 psia at 104 °F

    40 CFR 82.152 defines a low-pressure appliance by its refrigerant: a saturation pressure below 45 psia at 104 °F. The regulation's examples are R-11, R-123, R-113 and R-245fa.

    Source: 40 CFR 82.152 https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-F/section-82.152

  2. 2. Which refrigerant does the regulation list as an example of a low-pressure refrigerant?

    • A. R-410A
    • B. R-245fa
    • C. R-22
    • D. R-134a
    Show answer and explanation

    Answer: B. R-245fa

    The low-pressure examples in 82.152 are R-11, R-123, R-113 and R-245fa. R-134a is a medium-pressure example, and R-22 and R-410A are high-pressure examples.

    Source: 40 CFR 82.152 https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-F/section-82.152

  3. 3. What is the purpose of the purge unit on a low-pressure chiller?

    • A. To boost the condenser pressure for faster cooling
    • B. To remove air and other noncondensables that leak into the system
    • C. To add oil to the compressor
    • D. To measure the refrigerant charge
    Show answer and explanation

    Answer: B. To remove air and other noncondensables that leak into the system

    EPA's Type III topics include the purpose of the purge unit. Parts of a low-pressure system run below atmospheric pressure, so leaks pull air and moisture in rather than letting refrigerant out. The purge unit removes those noncondensables.

    Source: EPA, Section 608 Technician Certification Test Topics https://www.epa.gov/section608/section-608-technician-certification-test-topics

  4. 4. What's a telltale sign that a low-pressure chiller has a leak?

    • A. Excessive purging
    • B. Oil spots on the condenser
    • C. Frost on the discharge line
    • D. Unusually low superheat
    Show answer and explanation

    Answer: A. Excessive purging

    EPA's Type III topics name excessive purging as a sign of leakage into a low-pressure system. If the purge unit keeps running, air is getting in somewhere.

    Source: EPA, Section 608 Technician Certification Test Topics https://www.epa.gov/section608/section-608-technician-certification-test-topics

  5. 5. To leak test a low-pressure system, which pressurization method does EPA prefer first?

    • A. Compressed air
    • B. Nitrogen at the highest pressure available
    • C. Oxygen
    • D. Hot water, or a built-in system heating/pressurization device such as Prevac
    Show answer and explanation

    Answer: D. Hot water, or a built-in system heating/pressurization device such as Prevac

    EPA's Type III topics rank leak-test pressurization methods: first, the hot water method or a built-in heating/pressurization device such as Prevac; second, nitrogen. Heat raises the system's own refrigerant pressure without adding gases that later have to be purged.

    Source: EPA, Section 608 Technician Certification Test Topics https://www.epa.gov/section608/section-608-technician-certification-test-topics

  6. 6. Which comes second in EPA's order of preference for pressurizing a low-pressure system for a leak test?

    • A. Compressed air
    • B. Carbon dioxide from a fire extinguisher
    • C. R-22 vapor
    • D. Nitrogen
    Show answer and explanation

    Answer: D. Nitrogen

    After hot water or a built-in heating/pressurization device, EPA's Type III topics list nitrogen. Don't exceed the equipment manufacturer's limits when pressurizing a chiller for a leak test.

    Source: EPA, Section 608 Technician Certification Test Topics https://www.epa.gov/section608/section-608-technician-certification-test-topics

22 more questions load when you start a round.

Who needs EPA 608 Type III certification?

Anyone who maintains, services, repairs or disposes of low-pressure appliances needs Type III or Universal certification (40 CFR 82.161). That's mostly commercial chiller techs, building engineers in hospitals, campuses and office towers, and service techs for chiller manufacturers. A Type II card does not cover a low-pressure chiller.

A low-pressure appliance uses a refrigerant with a saturation pressure below 45 psia at 104 °F (40 CFR 82.152). The regulation lists R-11, R-123, R-113 and R-245fa as examples. If you never expect to touch a centrifugal chiller, you can skip Type III and stop at Type II. If your shop takes commercial work, Universal is usually worth the extra 25 questions.

Why low-pressure systems are their own section

In a high-pressure system, a leak lets refrigerant out. In a low-pressure chiller, parts of the system sit below atmospheric pressure, so a leak lets air and moisture in. Almost every Type III topic follows from that one fact:

  • Purge units exist to pull out the air and noncondensables that leak in. A purge unit that runs constantly is the standard sign of a leak.
  • Leak testing raises the system's pressure with heat first (hot water, or a built-in device such as Prevac), and only then nitrogen, according to EPA's topic list.
  • Water in the tubes can freeze as pressure drops during evacuation or as liquid flashes during charging. That's why you circulate or drain the water and charge vapor before liquid.
  • The evacuation target is absolute pressure, 25 mm Hg absolute, not inches of vacuum.

What's on the Type III section?

EPA 608 Type III topics and what to know
TopicWhat you should be able to answer
Leak detectionHot water or a built-in heating device first, then nitrogen; excessive purging as a sign of a leak; leak inspection and chronic-leaker reporting
Leak repairThresholds for chillers with 50+ lb of R-11 or R-123: 10% comfort cooling, 30% industrial process; the separate HFC rule for R-245fa-type systems
Recovery techniquesLiquid first, then vapor; heat oil to 130 °F before removing it; circulate or drain water to prevent freezing
RechargingVapor before liquid; charge centrifugals through the evaporator charging valve
Evacuation requirements25 mm Hg absolute; 0 psig for non-major repairs; the 85 °F boiling-point rule for how you may pressurize
Refrigeration and safetyPurpose of the purge unit; low-pressure PT relationships; ASHRAE 15 oxygen deprivation sensor plus a refrigerant sensor for R-123
Topics from EPA's official Type III list (2026-10-24).

The evacuation and pressurization rules for chillers

Table 1 of 40 CFR 82.156 sets one number for low-pressure appliances: 25 mm Hg absolute, for recovery equipment made before or after November 15, 1993 and at any charge size. That's simpler than Type II. The harder questions are about the opposite direction, raising pressure for a non-major repair.

Opening a low-pressure appliance (our summary of 40 CFR 82.156(a))
SituationWhat the rule requires
Major repair or disposalEvacuate to 25 mm Hg absolute and verify the level before opening
Non-major repair, not vented afterwardPressurize to no higher than 0 psig before opening; cover openings if you can't isolate
Refrigerant boils at or below 85 °F at atmospheric pressureDon't use methods such as nitrogen that need purging afterward
Refrigerant boils above 85 °F at atmospheric pressureUse heat to raise pressure as far as possible; nitrogen may make up the rest to atmospheric
Oil changeEvacuate or pressurize to no higher than 5 psig, or drain oil into a receiver brought to that limit
Leaks prevent reaching 25 mm HgIsolate; take leaking parts as low as you can without contaminating the refrigerant, never above 0 psig
Source: 40 CFR 82.156(a), verified 2026-10-24.

How are Type III questions different from Type II?

Type II rewards memorizing numbers. Type III rewards understanding why a chiller behaves the way it does. Many questions give you a symptom or a step and ask for the reason. Here's one from our bank:

Leak repair also reads differently here. Whenever a chiller holds 50 or more pounds of an ozone-depleting refrigerant such as R-11 or R-123, the 82.157 thresholds apply: 10% for comfort cooling, 30% for industrial process work. A chiller on R-245fa falls outside 82.157 but, since January 1, 2026, inside the AIM Act leak repair rule at 40 CFR 84.106.

How to study for Type III

  1. Start from "air leaks in." For any question, ask what a vacuum-side leak would do. That explains purging, the leak test order and why nitrogen is a second choice.
  2. Memorize the four temperatures and pressures in this section: 25 mm Hg absolute, 0 psig, 5 psig for oil changes, and 130 °F for oil heating. Add the 85 °F boiling-point line.
  3. Learn the order of operations: liquid out first, then vapor; vapor in first, then liquid; heat first, then nitrogen.
  4. Know the R-123 safety extra. ASHRAE 15 calls for a refrigerant sensor for R-123 on top of the oxygen deprivation sensor all equipment rooms need.
  5. Pair it with Type II. Most techs who need Type III also need Type II, and both together with Type I make Universal. Try the Universal practice test once each section clears 70%.

Frequently asked questions

What equipment does EPA 608 Type III cover?

Type III covers low-pressure appliances, defined as equipment using a refrigerant with a saturation pressure below 45 psia at 104 °F. In practice that means centrifugal chillers on refrigerants like R-11, R-123, R-113 and R-245fa.

Can a Type II tech work on a low-pressure chiller?

No. The regulation requires Type III or Universal certification to maintain, service, repair or dispose of low-pressure appliances. Type II covers medium-, high- and very high-pressure equipment only.

What vacuum level does Type III require before opening a chiller?

Before a major repair or disposal, a low-pressure appliance must be evacuated to 25 mm Hg absolute. The level is the same whether the recovery equipment was made before or after November 15, 1993.

Why do low-pressure chillers have purge units?

Parts of a low-pressure chiller operate below atmospheric pressure, so leaks draw in air and moisture. The purge unit removes those noncondensables. A purge unit that runs far more than normal is a sign the chiller is leaking.

Is Type III worth getting if I only do residential HVAC?

Strictly, no; residential systems are Type II equipment. But Universal certification requires Type III, so if you might work on chillers later, taking all three sections in one sitting gets you Universal without a second trip to a test site.

Sources

  1. EPA — Section 608 Technician Certification Test Topics (checked October 24, 2026)
  2. EPA — Section 608 Technician Certification Requirements (checked October 24, 2026)
  3. eCFR — 40 CFR 82.152 Definitions (checked October 24, 2026)
  4. eCFR — 40 CFR 82.156 Proper evacuation of refrigerant (Table 1) (checked October 24, 2026)
  5. eCFR — 40 CFR 82.157 Appliance maintenance and leak repair (checked October 24, 2026)
  6. eCFR — 40 CFR 84.106 Leak repair (AIM Act, HFCs) (checked October 24, 2026)
  7. eCFR — 40 CFR 82.161 Technician certification (checked October 24, 2026)
  8. eCFR — 40 CFR Part 82, Subpart F, Appendix D (test standards) (checked October 24, 2026)

Written by BRIX Editorial Team. Published October 24, 2026. Last updated October 24, 2026.

How we research and update pages: editorial policy.

Starting your own shop someday?
Start with the right setup.

When you go out on your own, BRIX answers the phone while you're on the job and keeps the books clean from the first invoice. Questions now? Call, text or book 15 minutes.

Prefer email? eeharris2004@gmail.com