Refrigerant PT Charts (Pressure-Temperature)
By BRIX Editorial Team · Updated
A refrigerant PT chart lists the pressure at which a refrigerant boils or condenses at each temperature. Techs use it to turn gauge pressures into saturation temperatures for superheat and subcooling. Pure refrigerants like R-32 and R-22 have one column; blends like R-454B have bubble (liquid) and dew (vapor) columns. Each refrigerant needs its own chart.
Key takeaways
- At 100°F the four refrigerants rank R-32 > R-410A > R-454B > R-22 by pressure. Using the wrong chart gives a believable but wrong answer.
- Dew (vapor) column for superheat, bubble (liquid) column for subcooling. On pure refrigerants they're the same number.
- Charts are in psig at sea level. At 5,000 ft the atmosphere is about 12.2 psia, so your gauge reads about 2.5 psi high against the chart.
- A PT chart gives saturation conditions, not a target charge. The equipment manufacturer's charging chart decides that.
- Every table here is computed with CoolProp 8.0.0 and tested against published Daikin and Arkema charts.
PT charts for each refrigerant
| Refrigerant | Type | ASHRAE class | GWP (EPA SNAP) | 40°F (dew) | 100°F (bubble) | Glide | U.S. status (Oct 2026) |
|---|---|---|---|---|---|---|---|
| R-410A | Blend, R-32/R-125 50/50 (near-azeotropic) | A1 | 2,090 | 118.4 | 318.5 | 0.2°F | HFC phasedown; new systems only from pre-2025 components |
| R-454B | Blend, R-32/R-1234yf 68.9/31.1 (zeotropic) | A2L | 470 | 107.5 | 303.3 | 2.7°F | Acceptable with use conditions for new AC/heat pumps |
| R-32 | Pure (single component) | A2L | 675 | 121.0 | 325.7 | 0 | Acceptable with use conditions for new AC/heat pumps |
| R-22 | Pure HCFC (single component) | A1 | Ozone-depleting HCFC | 68.6 | 195.9 | 0 | Production and import ended Jan 1, 2020; service with reclaimed |
How do you read a refrigerant PT chart?
Pick the chart for the refrigerant on the nameplate, then go from what you know to what you need. If you have a gauge pressure, find it in the pressure column and read the saturation temperature on that row. If you have a temperature, find its row and read the pressure. Between rows, interpolate, or use the refrigerant PT calculator, which does it for you.
- 1
Confirm the refrigerant.
Read the nameplate. R-410A, R-32 and R-454B equipment can look alike, and their charts are not interchangeable.
- 2
Choose the column.
On a blend, use dew (vapor) for anything on the suction side and bubble (liquid) for the liquid line. On R-32 or R-22 there's one column.
- 3
Convert the pressure.
Read the saturation temperature at your gauge pressure. Correct for altitude first if you're well above sea level.
- 4
Compare with the pipe.
Suction line temperature minus the dew point is superheat. Bubble point minus liquid line temperature is subcooling.
- 5
Judge against the target.
The target comes from the unit's charging chart or installation instructions, not from the PT chart.
Bubble point, dew point and glide
A single-component refrigerant boils at one temperature for each pressure. A blend of refrigerants with different boiling points doesn't: it starts boiling at the bubble point and finishes at the dew point, a little warmer. That spread is temperature glide. R-454B has about 2.7°F of it at typical suction pressure, enough to throw superheat off by that much if you read the wrong column. R-410A has about 0.2°F, which is why older R-410A charts printed a single column.
Do PT charts change with altitude?
The physics doesn't change, but your gauge does. PT charts are printed in psig relative to a sea-level atmosphere of 14.696 psia. A gauge zeroed at altitude reads relative to thinner air, so for the same saturation temperature it shows a higher number. Using NASA's standard-atmosphere model, the air is about 12.2 psia at 5,000 ft and 10.9 psia at 8,000 ft.
What a PT chart can't tell you
- Whether the charge is right. Pressure alone moves with indoor load and outdoor temperature. You need the line temperature too, and the manufacturer's target.
- Which refrigerant is in the system. A system topped off with the wrong refrigerant, or a mix, won't follow any chart. Recover it and recharge with the nameplate refrigerant.
- Normal operating pressures. A chart gives saturation pressure at a temperature. What a healthy system runs at depends on its design, airflow and conditions.
- Whether it's safe to retrofit. That's an EPA listing and manufacturer question, covered on the R-22 page.
How we build and check these charts
We don't copy manufacturer charts. Each table is computed from published equations of state with CoolProp 8.0.0, the open-source property library, from −40°F to 150°F in 5°F steps, and stored with the library version and date. Blends are modeled at their ASHRAE 34 compositions. An automated test suite then checks 20 temperatures per refrigerant against the Daikin A1 vs. A2L chart, plus the Arkema R-454B chart and the Arkema wall chart. R-22, R-32 and R-410A agree within 0.1 psi. R-454B agrees with Daikin within 1.4 psi and with Arkema within 1.5%, a smaller spread than the up-to-3-psi gap between those two manufacturers' own R-454B charts.
Tools that use these tables
Frequently asked questions
What is a PT chart used for in HVAC?
It converts between pressure and saturation temperature for a specific refrigerant. Techs use it to find the evaporator and condenser saturation temperatures from gauge readings, which they need to calculate superheat and subcooling and judge the charge.
Why do some PT charts have two columns?
Blends like R-454B and R-410A boil over a small temperature range, so each temperature has a bubble (liquid) pressure and a dew (vapor) pressure. Use dew for superheat and bubble for subcooling. Single-component refrigerants like R-32 and R-22 need only one column.
Which refrigerant has the highest pressure?
Of these four, at 100°F: R-32, then R-410A, then R-454B, then R-22. R-32 is 325.7 psig and R-22 is 195.9 psig at that temperature. Tools and gauges must be rated for the refrigerant you're working on.
Can I use an R-410A chart for R-454B?
No. R-454B runs lower pressure than R-410A, 107.5 vs 118.4 psig dew at 40°F, and it has more glide. Using the R-410A chart on an R-454B system misreads saturation temperature by several degrees.
Are PT charts in psig or psia?
Field PT charts, including these, are in psig: gauge pressure relative to a sea-level atmosphere of 14.696 psia. Add 14.696 for absolute pressure. At altitude, subtract the difference between 14.696 and local air pressure from your gauge reading before using the chart.
Why don't two PT charts match exactly?
Different charts use different property models and rounding, especially for blends. For R-22, R-32 and R-410A published charts agree within a tenth of a psi; for R-454B, Daikin's and Arkema's charts differ by up to about 3 psi near 100°F. When they disagree, follow the equipment manufacturer.
Related
- R-410A PT Chart (Pressure-Temperature)R-410A pressure-temperature chart from −40°F to 150°F in psig, computed with CoolProp, plus a quick lookup and what the 2026 EPA rule change means.
- R-454B PT Chart (Pressure-Temperature)R-454B pressure-temperature chart from −40°F to 150°F with bubble (liquid) and dew (vapor) psig, a quick lookup, °F/°C toggle and how to read glide.
- R-32 PT Chart (Pressure-Temperature)R-32 pressure-temperature chart, −40°F to 150°F in psig, one column because R-32 is a pure refrigerant. A2L safety notes, GWP 675 and a PT lookup.
- R-22 PT Chart (Pressure-Temperature)R-22 pressure-temperature chart from −40°F to 150°F in psig, plus where R-22 stands after EPA ended production in 2020 and what retrofits require.
- Refrigerant PT Calculator (Pressure ↔ Temperature)Convert refrigerant pressure to saturation temperature and back for R-410A, R-454B, R-32 and R-22, with bubble and dew points and an altitude correction.
- Superheat CalculatorFree superheat calculator: enter suction pressure and suction line temperature for R-410A, R-454B, R-32 or R-22 and compare with your target superheat.
- Subcooling CalculatorFree subcooling calculator: enter liquid line pressure and temperature for R-410A, R-454B, R-32 or R-22, using the bubble column, and check against target.
- Superheat and Subcooling, Explained with Worked ExamplesSuperheat and subcooling explained with worked R-454B and R-32 examples: which PT column to use, the formulas, common mistakes and five check questions.
- EPA Removes the January 1, 2026 R-410A Installation Deadline: What Contractors Need to KnowEPA's May 2026 rule ended the Jan. 1, 2026 deadline for installing pre-2025 R-410A split systems. What changed, what didn't, and the court challenges.
- HVAC Software That Answers the Phone, Books the Tech and Keeps the BooksHVAC software that answers every no-heat and no-cool call, books the tech, follows up on replacement quotes, chases invoices and keeps QuickBooks clean.
Sources
- CoolProp 8.0.0: thermophysical property library (HEOS backend), used to compute every table (checked October 24, 2026)
- Daikin Comfort Technologies: A1 vs. A2L Pressure Temperature Chart, USA (PM-A2LPTC-USA_04-24) (checked October 24, 2026)
- Arkema Forane: Pressure Temperature Chart, R-454B (PPC/SDC 05-2025) (checked October 24, 2026)
- Arkema Forane: refrigerant pressure-temperature wall chart, Americas (2019, NIST REFPROP 9.0) (checked October 24, 2026)
- U.S. EPA SNAP: Substitutes in residential and light commercial AC and heat pumps (GWP values) (checked October 24, 2026)
- U.S. EPA: Phaseout of Class II Ozone-Depleting Substances (HCFC-22) (checked October 24, 2026)
- NASA Glenn Research Center: Earth Atmosphere Model (troposphere pressure curve fit) (checked October 24, 2026)