R-410A PT Chart (Pressure-Temperature)
By BRIX Editorial Team · Updated
An R-410A PT chart gives the saturation pressure of R-410A at each temperature. R-410A is a near-azeotropic blend, so its liquid and vapor pressures differ by less than 1 psi and its glide is about 0.2°F. At 40°F it saturates at about 118.4 psig; at 100°F, about 318.5 psig.
Key takeaways
- R-410A is a 50/50 blend (by mass) of R-32 and R-125, classed A1 (lower toxicity, nonflammable).
- It's near-azeotropic: glide is only about 0.2°F, so one column is close enough for field work. The chart still shows both for precision.
- It runs about 63% higher pressure than R-22 at 100°F (318.5 vs 195.9 psig). Never use R-22 gauges, hoses or charts on it.
- EPA lists its GWP at 2,090, above the 700 GWP limit for new residential split systems built from components made after 2024.
- Pre-2025 R-410A inventory can still be installed since July 27, 2026, and existing systems can still be repaired.
R-410A PT lookup
- Bubble (liquid) pressure
- 118.8 psig
- Dew (vapor) pressure
- 118.4 psig
- Bubble minus dew
- 0.4 psi
At 40.0°F saturated R-410A vapor sits at 118.4 psig and saturated liquid at 118.8 psig. Use the dew pressure on the suction side (superheat) and the bubble pressure on the liquid side (subcooling).
| Temperature (°F) | Bubble / liquid (psig) | Dew / vapor (psig) |
|---|---|---|
| -40 | 10.8 | 10.7 |
| -35 | 14.1 | 14.0 |
| -30 | 17.8 | 17.7 |
| -25 | 21.9 | 21.8 |
| -20 | 26.3 | 26.2 |
| -15 | 31.2 | 31.0 |
| -10 | 36.5 | 36.3 |
| -5 | 42.2 | 42.0 |
| 0 | 48.4 | 48.2 |
| 5 | 55.2 | 54.9 |
| 10 | 62.4 | 62.2 |
| 15 | 70.3 | 70.0 |
| 20 | 78.7 | 78.4 |
| 25 | 87.7 | 87.4 |
| 30 | 97.4 | 97.0 |
| 35 | 107.7 | 107.3 |
| 40 | 118.8 | 118.4 |
| 45 | 130.6 | 130.1 |
| 50 | 143.2 | 142.6 |
| 55 | 156.5 | 156.0 |
| 60 | 170.7 | 170.1 |
| 65 | 185.8 | 185.1 |
| 70 | 201.8 | 201.1 |
| 75 | 218.7 | 217.9 |
| 80 | 236.5 | 235.8 |
| 85 | 255.4 | 254.6 |
| 90 | 275.4 | 274.5 |
| 95 | 296.4 | 295.5 |
| 100 | 318.5 | 317.6 |
| 105 | 341.9 | 340.9 |
| 110 | 366.4 | 365.4 |
| 115 | 392.3 | 391.2 |
| 120 | 419.4 | 418.3 |
| 125 | 447.9 | 446.8 |
| 130 | 477.9 | 476.8 |
| 135 | 509.4 | 508.3 |
| 140 | 542.5 | 541.4 |
| 145 | 577.3 | 576.3 |
| 150 | 613.9 | 613.0 |
What are normal R-410A pressures at 40°F and 100°F?
At a 40°F saturation temperature, typical of a cooling-mode evaporator, R-410A sits at 118.4 psig. At a 100°F condensing temperature it's 318.5 psig. Those are saturation pressures, not targets: what a running system shows depends on indoor load, airflow and outdoor temperature, so you judge charge by superheat or subcooling against the manufacturer's chart.
| Saturation temp | R-410A (dew) | R-32 | R-454B (dew) | R-22 |
|---|---|---|---|---|
| 0°F | 48.2 | 49.3 | 42.9 | 24.0 |
| 40°F | 118.4 | 121.0 | 107.5 | 68.6 |
| 100°F | 317.6 | 325.7 | 291.9 | 195.9 |
Does R-410A have glide? Bubble vs. dew
Barely. R-410A's two components, R-32 and R-125, boil at almost the same temperature at a given pressure, so the blend acts nearly like a single refrigerant. In this table the bubble-to-dew gap is about 0.2°F at 118 psig and 0.2°F at 340 psig; in pressure terms it's 0.9 psi at 100°F (318.5 bubble, 317.6 dew). Daikin's published chart shows the same split (318.6 liquid, 317.6 vapor).
Even with small glide, R-410A is still a blend. Charge it as liquid unless the manufacturer says otherwise, so the mix going into the system stays at 50/50.
Is R-410A being phased out?
R-410A is being phased down, not banned outright. The AIM Act has EPA cut U.S. HFC production and consumption by 85% by 2036 through allowances, which shrinks the supply of R-410A over time. Separately, EPA's Technology Transitions rules set a 700 GWP limit for new residential and light commercial AC and heat pump systems, and EPA lists R-410A's GWP at 2,090.
- New systems from current production: components made or imported on or after January 1, 2025 can't go in as a new R-410A system. They use an A2L like R-454B or R-32 instead.
- Pre-2025 inventory: EPA's final rule effective July 27, 2026 removed the January 1, 2026 installation deadline for systems whose specified components were all made or imported before January 1, 2025. Details, dates and the pending court petitions are in our news post on the R-410A deadline change.
- Repairs: EPA's FAQ says existing systems can keep being serviced, including replacing a major component like a condensing unit or compressor.
- Self-contained products such as window units follow a different schedule on EPA's sector table.
How this table was made and checked
We compute every row with CoolProp 8.0.0 (HEOS backend) as an R-32/R-125 mixture at 50/50% by mass, then convert to gauge pressure relative to 14.696 psia. Our automated test compares 20 temperatures from −30°F to 150°F against the Daikin A1 vs. A2L chart (liquid and vapor columns, all within 0.1 psi) and 10 temperatures against the Arkema Forane wall chart, which was generated with NIST REFPROP. At 0°F the table reads 48.4 psig liquid and 48.2 psig vapor; both published charts print 48.4 liquid.
Frequently asked questions
What should R-410A pressure be at 40°F?
About 118.4 psig (vapor) and 118.8 psig (liquid) at a 40°F saturation temperature. That's what a cooling coil boiling at 40°F would read on the suction gauge at sea level. Whether that's right for the unit depends on load and airflow, so check superheat or subcooling against the manufacturer's chart.
Is R-410A a blend or a pure refrigerant?
It's a blend of R-32 and R-125, 50/50 by mass. It's near-azeotropic, with about 0.2°F of glide, so it behaves almost like a single refrigerant. It should still be charged as liquid so the composition doesn't shift.
Can I still buy and install R-410A in 2026?
R-410A refrigerant is still sold for servicing, though the AIM Act phasedown is shrinking supply. Since July 27, 2026, new R-410A split systems can be installed if every specified component was made or imported before January 1, 2025. Systems built from 2025-or-later components need a refrigerant under 700 GWP.
Can I put R-454B or R-32 in an R-410A system?
No. Both are A2L (mildly flammable) refrigerants approved for new equipment designed for them, and their pressures differ from R-410A. Use the refrigerant on the nameplate and never mix refrigerants in a system.
Why is R-410A pressure so much higher than R-22?
R-410A has a higher vapor pressure at the same temperature: 318.5 psig at 100°F against 195.9 psig for R-22, about 63% higher. That's why R-410A equipment, gauges, hoses and recovery cylinders are rated for higher pressure.
Which column do I use on an R-410A chart?
Technically dew (vapor) for superheat and bubble (liquid) for subcooling, like any blend. On R-410A the difference is only about 0.2°F, which is why many older R-410A charts print one column.
Related
- Refrigerant PT Charts (Pressure-Temperature)Refrigerant pressure-temperature charts for R-410A, R-454B, R-32 and R-22, computed with CoolProp, plus a side-by-side comparison and how to read them.
- R-454B PT Chart (Pressure-Temperature)R-454B pressure-temperature chart from −40°F to 150°F with bubble (liquid) and dew (vapor) psig, a quick lookup, °F/°C toggle and how to read glide.
- R-32 PT Chart (Pressure-Temperature)R-32 pressure-temperature chart, −40°F to 150°F in psig, one column because R-32 is a pure refrigerant. A2L safety notes, GWP 675 and a PT lookup.
- R-22 PT Chart (Pressure-Temperature)R-22 pressure-temperature chart from −40°F to 150°F in psig, plus where R-22 stands after EPA ended production in 2020 and what retrofits require.
- Refrigerant PT Calculator (Pressure ↔ Temperature)Convert refrigerant pressure to saturation temperature and back for R-410A, R-454B, R-32 and R-22, with bubble and dew points and an altitude correction.
- Superheat CalculatorFree superheat calculator: enter suction pressure and suction line temperature for R-410A, R-454B, R-32 or R-22 and compare with your target superheat.
- Subcooling CalculatorFree subcooling calculator: enter liquid line pressure and temperature for R-410A, R-454B, R-32 or R-22, using the bubble column, and check against target.
- EPA Removes the January 1, 2026 R-410A Installation Deadline: What Contractors Need to KnowEPA's May 2026 rule ended the Jan. 1, 2026 deadline for installing pre-2025 R-410A split systems. What changed, what didn't, and the court challenges.
- Superheat and Subcooling, Explained with Worked ExamplesSuperheat and subcooling explained with worked R-454B and R-32 examples: which PT column to use, the formulas, common mistakes and five check questions.
- HVAC Software That Answers the Phone, Books the Tech and Keeps the BooksHVAC software that answers every no-heat and no-cool call, books the tech, follows up on replacement quotes, chases invoices and keeps QuickBooks clean.
Sources
- CoolProp 8.0.0: thermophysical property library (HEOS backend), used to compute this table (checked October 24, 2026)
- Daikin Comfort Technologies: A1 vs. A2L Pressure Temperature Chart, USA (PM-A2LPTC-USA_04-24) (checked October 24, 2026)
- Arkema Forane: refrigerant pressure-temperature wall chart, Americas (2019, NIST REFPROP 9.0) (checked October 24, 2026)
- U.S. EPA SNAP: Substitutes in residential and light commercial AC and heat pumps (R-410A GWP 2,090) (checked October 24, 2026)
- U.S. EPA: HFC allowance allocation and reporting (AIM Act, 85% phasedown by 2036) (checked October 24, 2026)
- U.S. EPA: Frequent questions on the phasedown of HFCs (repairs to existing systems) (checked October 24, 2026)
- U.S. EPA: Technology Transitions HFC restrictions by sector (checked October 24, 2026)