R-454B PT Chart (Pressure-Temperature)

By BRIX Editorial Team · Updated

An R-454B PT chart lists the pressure at which R-454B boils or condenses at each temperature. Because R-454B is a blend with about 2.5–2.7°F of glide, it has two columns: bubble (liquid) and dew (vapor). Use dew pressure for superheat and bubble pressure for subcooling. At 40°F, dew is 107.5 psig.

Key takeaways

  • R-454B is a zeotropic blend of R-32 and R-1234yf (68.9/31.1% by mass), so each temperature has a bubble and a dew pressure.
  • Use the dew column on the suction side (superheat) and the bubble column on the liquid side (subcooling).
  • Glide is about 2.7°F at a typical suction pressure and 2.6°F at a typical liquid-line pressure.
  • R-454B runs lower pressures than R-410A: at 40°F its dew pressure is 107.5 psig against 118.4 psig for R-410A.
  • Always confirm charge against the equipment manufacturer's charging chart and installation instructions.

R-454B PT lookup

°F
Dew (vapor) pressure at 40.0°F107.5 psig
Bubble (liquid) pressure
113.2 psig
Dew (vapor) pressure
107.5 psig
Bubble minus dew
5.7 psi

At 40.0°F saturated R-454B vapor sits at 107.5 psig and saturated liquid at 113.2 psig. Use the dew pressure on the suction side (superheat) and the bubble pressure on the liquid side (subcooling).

R-454B saturation pressure by temperature (°F, psig)
Temperature (°F)Bubble / liquid (psig)Dew / vapor (psig)
-409.88.5
-3513.011.5
-3016.614.9
-2520.518.6
-2024.722.7
-1529.427.1
-1034.532.0
-540.037.2
045.942.9
552.449.1
1059.355.7
1566.862.9
2074.870.6
2583.578.9
3092.787.8
35102.697.3
40113.2107.5
45124.5118.3
50136.4129.9
55149.2142.2
60162.7155.3
65177.1169.2
70192.3183.9
75208.4199.5
80225.4216.0
85243.4233.5
90262.3251.9
95282.3271.4
100303.3291.9
105325.4313.5
110348.6336.3
115373.0360.3
120398.6385.5
125425.5412.1
130453.6440.0
135483.1469.3
140514.1500.2
145546.4532.6
150580.3566.8
Computed with CoolProp 8.0.0 (HEOS equations of state) on 2026-10-24, as R-32 68.9% / R-1234yf 31.1% by mass. Gauge pressure relative to 14.696 psia (sea level). Verify against the equipment manufacturer's installation instructions.

How do you read an R-454B PT chart?

Find the temperature in the left column, then read across. The bubble (liquid) column is the pressure where liquid R-454B starts to boil. The dew (vapor) column is the pressure where the last drop has boiled off. For a single-component refrigerant like R-32 or R-22 those are the same number. For R-454B they differ by several psi, so you have to pick the right column for the side of the system you're measuring.

  1. 1

    Suction side: use dew.

    Read suction pressure at the service valve, look up the dew (vapor) saturation temperature, and subtract it from the suction line temperature. That's superheat.

  2. 2

    Liquid side: use bubble.

    Read liquid line pressure, look up the bubble (liquid) saturation temperature, and subtract the liquid line temperature from it. That's subcooling.

  3. 3

    Compare with the target.

    The target superheat or subcooling comes from the unit's charging chart or nameplate, not from the PT chart. Fixed-orifice systems usually charge by superheat and TXV/EEV systems by subcooling, but follow the manufacturer.

What is temperature glide in R-454B?

Glide is the temperature difference between the bubble point and the dew point at one pressure. R-454B's two components boil at different temperatures, so as it evaporates the remaining liquid gets richer in the less volatile one and the boiling temperature climbs. In this table that works out to about 2.7°F at 110 psig and 2.6°F at 330 psig. For example, at 118.3 psig the dew point is 45.0°F and the bubble point is 42.3°F.

In pressure terms the gap is larger: at 100°F the bubble pressure is 303.3 psig and the dew pressure is 291.9 psig. Reading the wrong column overstates or understates superheat and subcooling by roughly the glide, which is enough to push a charge decision the wrong way. Because the blend can fractionate, charge it as liquid unless the manufacturer says otherwise.

Is R-454B flammable? A2L safety notes

R-454B carries the ASHRAE safety classification A2L: lower toxicity (A) and lower flammability (2L). Under ASHRAE Standard 34, a 2L refrigerant has a maximum burning velocity of 10 cm/s or less when tested at 23°C and 101.3 kPa. 2L is the lowest flammability class above nonflammable (class 1), but a 2L refrigerant can still burn.

  • EPA lists R-454B as acceptable with use conditions for new residential and light commercial air conditioning and heat pumps, with a GWP of 470 (EPA SNAP). The use conditions are in the May 6, 2021 rule.
  • Per EPA SNAP approvals, A2L refrigerants go in new equipment designed for them only. Don't retrofit R-454B into an R-410A system and never mix refrigerants (Daikin A2L PT chart).
  • Use recovery equipment, cylinders and leak detectors rated for A2L refrigerants, keep ignition sources away from the work area, and ventilate before brazing.
  • The equipment manufacturer's installation instructions and your local code set the rules for leak detection, charge limits and labeling on a given unit.

Where these numbers come from

We compute the table ourselves with CoolProp 8.0.0, an open-source thermophysical property library, using its Helmholtz-energy equations of state for an R-32/R-1234yf mixture at the ASHRAE 34 composition (68.9/31.1% by mass). Pressures are gauge (psig), relative to a standard atmosphere of 14.696 psia; at altitude your gauge reads differently for the same saturation temperature.

How this table compares with two published R-454B charts (psig)
PointThis chart (CoolProp)Daikin A2L chart (2024)Arkema Forane chart (2025)
40°F bubble / liquid113.2113.3112.0
40°F dew / vapor107.5107.7107.0
100°F bubble / liquid303.3303.6300.8
100°F dew / vapor291.9291.6290.9
Our test suite checks 20 temperatures from −30°F to 150°F against the Daikin chart (all within ±2 psi) and the Arkema chart (within 1.5%). The two manufacturer charts differ from each other by up to about 3 psi near 100°F, because each uses its own mixture model.

Frequently asked questions

What should R-454B pressures be?

It depends on the saturation temperature you need. At 40°F, R-454B's dew pressure is about 107.5 psig, and at 100°F its bubble pressure is about 303.3 psig. Operating pressures on a running system depend on load, airflow and outdoor temperature, so judge the charge by superheat or subcooling against the manufacturer's chart.

Which column do I use for superheat on R-454B?

Use the dew (vapor) column. Superheat is measured on the suction line, where the refrigerant has finished boiling, so the saturation temperature that matters is the dew point. For subcooling on the liquid line, use the bubble (liquid) column.

How much glide does R-454B have?

About 2.7°F at typical suction pressures and 2.6°F at typical liquid-line pressures, based on this table. That's small compared with high-glide refrigeration blends, but large enough that using the wrong column throws superheat or subcooling off by a couple of degrees.

Is R-454B higher or lower pressure than R-410A?

Lower. At 40°F, R-454B's dew pressure is 107.5 psig against 118.4 psig for R-410A, and the gap widens at higher temperatures. Don't use an R-410A chart on an R-454B system, and use gauges and tools listed for A2L refrigerants.

Can I put R-454B in an R-410A system?

No. Per EPA SNAP approvals, A2L refrigerants like R-454B can only be used in new equipment designed for them, not retrofitted into an existing system. Always use the refrigerant on the nameplate and never mix refrigerants.

Why don't the numbers match my other PT chart exactly?

Published R-454B charts use different mixture models and rounding, so they differ by a few psi at high temperatures. Daikin's and Arkema's charts differ from each other by up to about 3 psi near 100°F. Our values fall within that spread. When in doubt, follow the equipment manufacturer's chart.

Sources

  1. CoolProp 8.0.0: thermophysical property library (HEOS backend), used to compute this table (checked October 24, 2026)
  2. Daikin Comfort Technologies: A1 vs. A2L Pressure Temperature Chart, USA (PM-A2LPTC-USA_04-24) (checked October 24, 2026)
  3. Arkema Forane: Pressure Temperature Chart, R-454B (PPC/SDC 05-2025) (checked October 24, 2026)
  4. U.S. EPA SNAP: Substitutes in residential and light commercial air conditioning and heat pumps (checked October 24, 2026)
  5. ANSI/ASHRAE Addendum ak to Standard 34-2007: A2L / 2L burning velocity ≤ 10 cm/s (checked October 24, 2026)