R-32 PT Chart (Pressure-Temperature)
By BRIX Editorial Team · Updated
An R-32 PT chart lists the saturation pressure of R-32 (difluoromethane) at each temperature. R-32 is a single-component refrigerant, so liquid and vapor saturate at the same pressure and the chart needs only one column. At 40°F, R-32 is about 121.0 psig; at 100°F, about 325.7 psig.
Key takeaways
- R-32 is a pure fluid: no glide, no bubble and dew columns, and a leak doesn't change the composition of what's left.
- It runs slightly above R-410A: 2.6 psi higher at 40°F and 7.2 psi higher at 100°F.
- EPA SNAP lists R-32 as acceptable with use conditions for new residential and light commercial AC and heat pumps, GWP 675.
- ASHRAE safety class A2L: lower toxicity, lower flammability. Use A2L-rated tools and follow the installation instructions.
- It's the main ingredient in both R-410A (50% by mass) and R-454B (68.9%).
R-32 PT lookup
- Saturation pressure
- 121.0 psig
R-32 is a single-component refrigerant, so liquid and vapor saturate at the same pressure: 121.0 psig at 40.0°F.
| Temperature (°F) | Pressure (psig) |
|---|---|
| -40 | 11.0 |
| -35 | 14.4 |
| -30 | 18.2 |
| -25 | 22.3 |
| -20 | 26.8 |
| -15 | 31.7 |
| -10 | 37.1 |
| -5 | 42.9 |
| 0 | 49.3 |
| 5 | 56.1 |
| 10 | 63.5 |
| 15 | 71.4 |
| 20 | 80.0 |
| 25 | 89.2 |
| 30 | 99.1 |
| 35 | 109.7 |
| 40 | 121.0 |
| 45 | 133.0 |
| 50 | 145.8 |
| 55 | 159.5 |
| 60 | 174.0 |
| 65 | 189.5 |
| 70 | 205.8 |
| 75 | 223.2 |
| 80 | 241.5 |
| 85 | 260.9 |
| 90 | 281.3 |
| 95 | 302.9 |
| 100 | 325.7 |
| 105 | 349.6 |
| 110 | 374.9 |
| 115 | 401.4 |
| 120 | 429.3 |
| 125 | 458.7 |
| 130 | 489.5 |
| 135 | 521.8 |
| 140 | 555.8 |
| 145 | 591.4 |
| 150 | 628.8 |
Why does an R-32 chart have only one pressure column?
Because R-32 is one molecule, not a mixture. A pure refrigerant boils and condenses at the same temperature for a given pressure, so the bubble point and the dew point are identical. There's no glide to account for, and you use the same number whether you're working out superheat on the suction line or subcooling on the liquid line.
That also makes the field side simpler than a blend. A slow leak can't fractionate R-32, so after the leak is repaired the remaining charge is still R-32. Follow the manufacturer's charging and recovery instructions all the same, since A2L handling rules apply.
R-32 vs. R-410A and R-454B pressures
| Saturation temp | R-32 | R-410A | R-454B | R-32 minus R-410A |
|---|---|---|---|---|
| 0°F | 49.3 | 48.2 | 42.9 | +1.1 |
| 20°F | 80.0 | 78.4 | 70.6 | +1.6 |
| 40°F | 121.0 | 118.4 | 107.5 | +2.6 |
| 70°F | 205.8 | 201.1 | 183.9 | +4.7 |
| 100°F | 325.7 | 317.6 | 291.9 | +8.1 |
| 120°F | 429.3 | 418.3 | 385.5 | +11.0 |
Is R-32 flammable? What A2L means
Yes, mildly. R-32 carries the ASHRAE safety class A2L: A for lower toxicity, 2L for lower flammability. ASHRAE Standard 34 defines 2L as a maximum burning velocity of 10 cm/s or less, tested at 23°C and 101.3 kPa. It's harder to ignite and burns more slowly than a class 2 or 3 refrigerant, but it isn't nonflammable like R-22 or R-410A (both A1).
- EPA status: EPA SNAP lists R-32 as acceptable with use conditions for new residential and light commercial AC and heat pumps, with a GWP of 675 and an ozone depletion potential of 0. The listings are in Federal Register rules dated April 10, 2015, May 6, 2021 and April 28, 2023.
- New equipment only: use R-32 in equipment designed and listed for it. Don't convert an R-410A or R-22 system to R-32, and never mix refrigerants.
- Tools: recovery machines, cylinders, vacuum pumps and leak detectors should be rated for A2L refrigerants. Keep ignition sources out of the work area and ventilate before brazing.
- Install rules such as charge limits, leak detection and mitigation come from the equipment's installation instructions and your adopted codes.
Where these numbers come from
We compute the table with CoolProp 8.0.0 using its reference equation of state for pure R-32, converted to gauge pressure relative to 14.696 psia. Our tests compare 20 temperatures against the Daikin A1 vs. A2L chart and 10 against the Arkema Forane wall chart (NIST REFPROP 9.0); every point is within 0.1 psi. At 0°F we compute 49.3 psig; Daikin prints 49.2 and Arkema 49.3.
Frequently asked questions
What is the pressure of R-32 at 40°F?
About 121.0 psig at sea level. Because R-32 is a pure refrigerant, that's both the liquid and the vapor saturation pressure. A running system's suction pressure depends on load and airflow, so check the charge with superheat or subcooling against the manufacturer's chart.
Does R-32 have temperature glide?
No. R-32 is a single-component refrigerant, so it boils and condenses at one temperature for each pressure. That's why its PT chart has one pressure column, unlike R-454B or R-410A.
Is R-32 higher pressure than R-410A?
Slightly. At 40°F R-32 is 121.0 psig against 118.4 for R-410A, and at 100°F it's 325.7 against 318.5. Use the R-32 chart and gauges rated for R-32 rather than reading an R-410A chart.
What is the GWP of R-32?
EPA's SNAP listing for residential and light commercial AC and heat pumps gives R-32 a GWP of 675, under the 700 limit for new systems, and an ozone depletion potential of 0.
Can R-32 replace R-410A in an existing system?
No. R-32 is an A2L refrigerant approved for new equipment designed for it. Converting an R-410A system isn't an approved retrofit, and mixing refrigerants is never acceptable. Use the refrigerant on the nameplate.
Is R-32 the same as R-454B?
No. R-454B is a blend that's 68.9% R-32 by mass, with R-1234yf making up the rest. It runs lower pressures than R-32 and has about 2.5–2.7°F of glide, so the two charts aren't interchangeable.
Related
- Refrigerant PT Charts (Pressure-Temperature)Refrigerant pressure-temperature charts for R-410A, R-454B, R-32 and R-22, computed with CoolProp, plus a side-by-side comparison and how to read them.
- R-454B PT Chart (Pressure-Temperature)R-454B pressure-temperature chart from −40°F to 150°F with bubble (liquid) and dew (vapor) psig, a quick lookup, °F/°C toggle and how to read glide.
- R-410A PT Chart (Pressure-Temperature)R-410A pressure-temperature chart from −40°F to 150°F in psig, computed with CoolProp, plus a quick lookup and what the 2026 EPA rule change means.
- R-22 PT Chart (Pressure-Temperature)R-22 pressure-temperature chart from −40°F to 150°F in psig, plus where R-22 stands after EPA ended production in 2020 and what retrofits require.
- Refrigerant PT Calculator (Pressure ↔ Temperature)Convert refrigerant pressure to saturation temperature and back for R-410A, R-454B, R-32 and R-22, with bubble and dew points and an altitude correction.
- Superheat CalculatorFree superheat calculator: enter suction pressure and suction line temperature for R-410A, R-454B, R-32 or R-22 and compare with your target superheat.
- Subcooling CalculatorFree subcooling calculator: enter liquid line pressure and temperature for R-410A, R-454B, R-32 or R-22, using the bubble column, and check against target.
- Superheat and Subcooling, Explained with Worked ExamplesSuperheat and subcooling explained with worked R-454B and R-32 examples: which PT column to use, the formulas, common mistakes and five check questions.
- Free EPA 608 Core Practice TestFree EPA 608 Core practice test: 36 original questions with explanations, study and exam modes, and a score by topic. No sign-up.
- HVAC Software That Answers the Phone, Books the Tech and Keeps the BooksHVAC software that answers every no-heat and no-cool call, books the tech, follows up on replacement quotes, chases invoices and keeps QuickBooks clean.
Sources
- CoolProp 8.0.0: thermophysical property library (HEOS backend), used to compute this table (checked October 24, 2026)
- Daikin Comfort Technologies: A1 vs. A2L Pressure Temperature Chart, USA (PM-A2LPTC-USA_04-24) (checked October 24, 2026)
- Arkema Forane: refrigerant pressure-temperature wall chart, Americas (2019, NIST REFPROP 9.0) (checked October 24, 2026)
- U.S. EPA SNAP: Substitutes in residential and light commercial AC and heat pumps (R-32: acceptable with use conditions, GWP 675) (checked October 24, 2026)
- ANSI/ASHRAE Addendum ak to Standard 34-2007: A2L / 2L burning velocity ≤ 10 cm/s (checked October 24, 2026)