R-22 PT Chart (Pressure-Temperature)

By BRIX Editorial Team · Updated

An R-22 PT chart lists the saturation pressure of R-22 (HCFC-22) at each temperature. R-22 is a single-component refrigerant, so one pressure column covers both liquid and vapor. At 40°F it's about 68.6 psig and at 100°F about 195.9 psig. U.S. production and import of R-22 ended January 1, 2020.

Key takeaways

  • R-22 is a pure HCFC refrigerant with one pressure column and no glide, classed A1 (lower toxicity, nonflammable).
  • EPA: U.S. production and import of HCFC-22 ended January 1, 2020. Owners can keep using existing systems for as long as necessary.
  • Service supply now comes from recovered and reclaimed R-22 plus R-22 produced before 2020.
  • R-22 runs much lower pressure than R-410A: 195.9 vs 318.5 psig at 100°F. The equipment, gauges and charts aren't interchangeable.
  • "R-22a" is not R-22. EPA says it's a flammable hydrocarbon blend and not an acceptable alternative.

R-22 PT lookup

°F
Saturation pressure at 40.0°F68.6 psig
Saturation pressure
68.6 psig

R-22 is a single-component refrigerant, so liquid and vapor saturate at the same pressure: 68.6 psig at 40.0°F.

R-22 saturation pressure by temperature (°F, psig)
Temperature (°F)Pressure (psig)
-400.6
-352.6
-304.9
-257.4
-2010.2
-1513.2
-1016.5
-520.1
024.0
528.3
1032.8
1537.8
2043.1
2548.8
3055.0
3561.5
4068.6
4576.1
5084.1
5592.6
60101.6
65111.2
70121.4
75132.2
80143.6
85155.7
90168.4
95181.8
100195.9
105210.8
110226.4
115242.8
120260.0
125278.0
130296.9
135316.7
140337.4
145359.0
150381.7
Computed with CoolProp 8.0.0 (HEOS equations of state) on 2026-10-24. Gauge pressure relative to 14.696 psia (sea level). Verify against the equipment manufacturer's installation instructions.

How do you use an R-22 PT chart on an older system?

Convert each gauge pressure to its saturation temperature and compare it with the pipe temperature. Because R-22 is a single compound, the same chart column works on both sides of the system: suction pressure gives the evaporator's boiling temperature, and liquid-line pressure gives the condensing temperature.

At the cold end, R-22 is close to atmospheric pressure: the table shows 0.6 psig at −40°F. Low-temperature R-22 equipment can pull the suction side into a vacuum, which a compound gauge shows in inches of mercury. Air-conditioning evaporators run far above that range.

Yes, in existing equipment. EPA's homeowner fact sheet says U.S. production and import of HCFC-22 ended on January 1, 2020, "but you may continue to use HCFC-22 in your existing system for as long as necessary" (EPA-430-FR-20001). No federal rule requires an owner to replace a working R-22 system.

HCFC-22 phaseout milestones (U.S.)
DateWhat changedSource
January 1, 2010No production or import of HCFC-22 except for use in equipment manufactured before January 1, 2010EPA Class II phaseout page
January 1, 2020No production or import of HCFC-22EPA Class II phaseout page
Since 2020Existing systems are served by recovered and reclaimed HCFC-22 and HCFC-22 produced before 2020EPA fact sheet
EPA's Class II page also lists blends containing HCFC-22 (R-401A, R-402A, R-408A, R-409A, R-414B, R-502A) as subject to the same rules. Page last updated April 1, 2026; read October 24, 2026.
  • Venting is illegal. Under Section 608 of the Clean Air Act, it's illegal to knowingly vent or release refrigerant while servicing, repairing or disposing of AC equipment. Recover it.
  • Supply is finite. With no new production, every pound used for service comes out of recovered, reclaimed or pre-2020 stock. Leak repair is the cheapest way to keep an R-22 system running.
  • Watch for fakes. EPA warns that "R-22a" has been falsely marketed as R-22 or an R-22 replacement. It's a hydrocarbon blend whose main components include propane and butane, highly flammable, and not an acceptable alternative for residential AC.

What about converting an R-22 system to another refrigerant?

EPA's SNAP program lists non-ozone-depleting alternatives for residential AC. EPA's fact sheet notes that some are for new systems only, while others are listed for both new and retrofitted systems. We don't call any of them a "drop-in": EPA's guidance for a retrofit is that the technician recovers all remaining R-22, follows the manufacturer's handling and installation guidelines for that specific alternative, and explains how the conversion may change the system's performance and energy use.

  • Check the replacement refrigerant manufacturer's retrofit guide for oil, seals, metering device and charge instructions before quoting a conversion.
  • Never put R-410A, R-32 or R-454B in an R-22 system. They run at much higher pressures and are listed for new equipment designed for them.
  • Never mix a replacement refrigerant with leftover R-22. Recover first, then charge the new refrigerant to its own PT chart.
  • Label the system with the new refrigerant so the next tech doesn't read the wrong chart.

How this table was made and checked

We compute the table with CoolProp 8.0.0 using its equation of state for pure R-22, converted to gauge pressure relative to 14.696 psia. Our tests compare 20 temperatures against the Daikin A1 vs. A2L chart and 10 against the Arkema Forane wall chart (NIST REFPROP 9.0). Every point matches within 0.1 psi; at 100°F all three read 195.9 psig.

Frequently asked questions

What should R-22 pressure be at 40°F?

About 68.6 psig. That's the saturation pressure of R-22 at 40°F, which is roughly where an AC evaporator boils. Actual suction pressure depends on load and airflow, so check the charge with superheat or subcooling against the manufacturer's chart.

Is R-22 banned?

U.S. production and import of R-22 ended January 1, 2020. Using and servicing existing R-22 systems is still allowed, with recovered, reclaimed or pre-2020 refrigerant, according to EPA. Venting it is illegal.

Can I put R-410A in an R-22 system?

No. R-410A runs about 1.6 times the pressure of R-22 at 100°F (318.5 vs 195.9 psig), and R-22 equipment isn't built for it. Use only an alternative EPA lists for retrofit, following that refrigerant maker's retrofit instructions.

Is there a drop-in replacement for R-22?

EPA doesn't describe any alternative as a drop-in. It lists some substitutes for retrofitting existing systems and says the technician should recover all R-22, follow the manufacturer's guidelines for that alternative, and explain how performance and energy use may change.

Is R-22a the same as R-22?

No. EPA says R-22a has been falsely marketed as R-22 or a replacement for it. It's a hydrocarbon blend including propane and butane, highly flammable, and not an acceptable alternative for home air conditioners.

Does R-22 have glide?

No. R-22 is a single-component refrigerant, so it boils and condenses at one temperature for a given pressure. The chart has one column, and the same number works for superheat and subcooling.

Sources

  1. CoolProp 8.0.0: thermophysical property library (HEOS backend), used to compute this table (checked October 24, 2026)
  2. Daikin Comfort Technologies: A1 vs. A2L Pressure Temperature Chart, USA (PM-A2LPTC-USA_04-24) (checked October 24, 2026)
  3. Arkema Forane: refrigerant pressure-temperature wall chart, Americas (2019, NIST REFPROP 9.0) (checked October 24, 2026)
  4. U.S. EPA: Residential Air Conditioning and the Phaseout of HCFC-22, What You Need to Know (EPA-430-FR-20001, Feb 2020) (checked October 24, 2026)
  5. U.S. EPA: Phaseout of Class II Ozone-Depleting Substances (HCFC-22 milestones) (checked October 24, 2026)
  6. U.S. EPA SNAP: Substitutes in residential and light commercial AC and heat pumps (checked October 24, 2026)
  7. U.S. EPA: Section 608 of the Clean Air Act, stationary refrigeration and AC (checked October 24, 2026)